The new
Fluke 1555 insulation resistance tester offers digital insulation testing up to 10 kV, making it ideal for testing a wide range of high voltage equipment including switchgear, motors, generators and cables.
Fluke insulation testers can now conduct the entire range of test voltages specified in IEEE 43-2000 with a best in class, 3 year warranty and CAT IV 600 V safety rating. With measurement storage and PC interface, the 1555 is a perfect tool for preventative or predictive maintenance programs designed to identify potential equipment failures before they occur.
Applications
- Insulation resistance/leakage current measurement
- Step voltage testing
- Dielectric absorption ratio
- Polarization index
- Ramp voltage
For a 5kV model, see the
Fluke 1550C Insulation Resistance Tester.
What's Included:
- Test cables with alligator clips (red, black, green)
- Alligator clips
- Infrared adapter with interface cable
- FlukeView Forms basic CD-ROM
- AC power cord
- Soft carrying case
- Users manual on CD-ROM
- Quick Reference card
- English manual
- USB-IR cable installation guide
- FlukeView Forms installation guide
- Test voltages up to 10 kV provides solutions for all applications
- CAT III 1000 V, CAT IV 600 V safety rating
- Voltage breakdown detection alerts the user that voltage is present and gives the voltage reading up to 600 V ac or dc for increased user safety
- Selectable test voltages in 50 V steps from 250 to 1000 V, and 100 V steps above 1000 V
- Measurements can be stored in up to 99 memory locations, with each location assigned a unique, user defined, label for easy recall
- Long battery life gives the user over 750 tests between charges
- Automatic calculation of Dielectric Absorption (DAR) and Polarization Index (PI) with no additional setup
- Guard system eliminates the effect of surface leakage current on high-resistance measurements
- Large digital/analog LCD for easy viewing
- Capacitance and leakage current measurement
- Ramp function for breakdown testing
- Resistance measurements up to 2TΩ
- Timer settings up to 99 minutes for timed tests
- 3-year warranty
The Fluke 1555's accuracy is specified for one year after calibration at operating temperatures of 0 °C to 35 °C. For operating temperatures outside the range (-20 °C to 0 °C and 35 °C to 50 °C), add ± .25 % per °C, except on the 20 % bands add ± 1 % per °C.
Insulation Resistance Measurement
|
Test voltage (DC)
| Range (DC)
| Accuracy (± reading)
|
250 V
| < 200 kΩ 200 kΩ to 5 GΩ 5 GΩ to 50 GΩ > 50 GΩ
| unspecified 5 % 20 % unspecified
|
500 V
| < 200 kΩ 200 kΩ to 10 GΩ 10 GΩ to 100 GΩ > 100 GΩ
| unspecified 5 % 20 % unspecified
|
1000 V
| < 200 kΩ 200 kΩ to 20 GΩ 20 GΩ to 200 GΩ > 200 GΩ
| unspecified 5 % 20 % unspecified
|
2500 V
| < 200 kΩ 200 kΩ to 50 GΩ 50 GΩ to 500 GΩ > 500 GΩ
| unspecified 5 % 20 % unspecified
|
5000 V
| < 200 kΩ 200 kΩ to 100 GΩ 100 GΩ to 1 TΩ > 1 TΩ
| unspecified 5 % 20 % unspecified
|
10000 V
| < 200 kΩ 200 kΩ to 200 GΩ 10 GΩ to 2 TΩ > 2 TΩ
| unspecified 5 % 20 % unspecified
|
Bar graph range
| 0 to 1 TΩ
|
Insulation test voltage accuracy
| -0 %, +10 % at 1 mA load current
|
Induced ac mains current rejection
| 2 mA maximum
|
Charging rate for capacitive load
| 5 seconds per μF
|
Discharge rate for capacitive load
| 1.5 s/μF
|
| Range
| Accuracy
|
Leakage current measurement
| 1 nA to 2 mA
| ± (5 % + 2 nA)
|
Capacitance measurement
| 0.01 uF to 15.00 μF
| ± (15 % rdg + 0.03 μF)
|
Timer
| 0 to 99 minutes
| Resolution Setting: 1 minute Indication: 1 second
|
Live circuit warning
| Warning range 30 V to 660 V ac/dc, 50/60 Hz
| Voltage accuracy ± (15 % + 2 V)
|
General Specifications
|
Display
| 75 mm x 105 mm
|
Power
| 12 V lead-acid rechargeable battery, Yuasa NP2.8-12
|
Charger Input (AC)
| 85 V ac 50/60 Hz 20 VA
|
This Class II (double insulated) instrument is supplied with a Class 1 (grounded) power cord. The protective earth terminal (ground pin) is not connected internally. The extra pin is for added plug retention only.
|
Dimensions
| 170 mm x 242 mm x 330 mm (6.7 in x 9.5 in x 13 in)
|
Weight
| 3.6 kg (7.94 lb)
|
Temperature (operating)
| -20 ºC to 50 ºC (-4 ºF to 122 ºF)
|
Temperature (storage)
| -20 ºC to 65 ºC (-4 ºF to 149 ºF)
|
Humidity
| 80 % to 31 ºC decreasing linearly to 50 % at 50 ºC
|
Altitude
| 2000 m
|
Enclosure sealing
| IP40
|
Input overload protection
| 1000 V ac
|
Electromagnetic compatibility
| EN 61326
|
Certifications
| CSA CE, TUV-SUD
|
Safety compliance
| CAT III 1000 V, CAT IV 600 V
|
Pollution degree
| 2
|
Fluke ViewForms basic software requires a PC running Windows 2000, Windows XP and Windows Vista.