AEMC 6250 Micro-Ohmmeter 10A
please call (877)766-5412 to confirm




Resistance measurements are automatically calculated and displayed, taking into account the measurement value, ambient temperature, reference temperature and metal temperature coefficient. Sample temperature can be manually entered by the operator or directly measured by the AEMC 6250 with an external RTD temperature probe.
The AEMC 6250 Micro-Ohmmeter is uniquely designed to conduct tests on both resistive and inductive material, with operator selection directly from the front
panel. Three test modes are available; resistive (instantaneous test), inductive (continuous test), and auto (repetitive test). Up to 1500 measurements can be stored and printed directly to a printer of from a PC.
The large, easy-to-read display shows the resistance measurement, ambient and reference temperatures, metal type and test method, as well as alarm conditions and memory utilization, all in real time. Previously stored test results can easily be called up for review on the display or sent directly to a printer or remote terminal.
Two programmable alarm set points are available. Each can be either active high or low and will sound an alarm when tripped, further adding to the ease of use by permitting quick Pass/Fail measurements.
External trigger operation is available through the communication port allowing the test to be conducted from a remote location.
The AEMC 6250 Micro-Ohmmeter (10A) will be a valuable asset for your bond testing, coil and contact testing as well as coatings and connector or any other low resistance testing application.
Also see the AEMC 5600 digital low resistance ohmmeter (DLRO)
The Bad:
The Bottom Line:
Full Review
Resistive materials (i.e. ground bonding, coatings, contact resistances) are tested with an instantaneous test. Simply press the test button – the reading is taken and the test is concluded.
Inductive materials (i.e. coils, transformers, motor windings) are tested with a continuous test. The test is started and stopped by the operator at the push of a button.
Auto test mode is designed for multiple test points on resistive and/or low inductance material. The test is started at the press of a button. As the operator moves the probe from one point to another, the test is stopped, the results are displayed and a new test is started when the test probes again make contact – no need to press the test button! Residual voltage is measured between tests to ensure proper results. This test mode continues until the operator presses the button to conclude the testing.
Other Features:
|
MODEL |
|
|
|
6250 |
|
|
|
|
|||
|
ELECTRICAL |
|
|
|
|
|
|
|
|
|||
|
Range |
5.0000mΩ |
25.000mΩ |
250.00mΩ |
2500.0mΩ |
25.000Ω |
250.00Ω |
2500.0Ω |
|
|||
|
Accuracy |
0.05% + 0.5µΩ |
0.05% + 3µΩ |
0.05% + 30µΩ |
0.05% + 0.3mΩ |
0.05% + 3mΩ |
0.05% + 30mΩ |
0.05% + 300mΩ |
|
|||
|
Resolution |
0.1µΩ |
1µΩ |
10µΩ |
0.1mΩ |
1mΩ |
10mΩ |
100mΩ |
|
|||
|
Test Current |
10A |
10A |
10A |
1A |
100mA |
10mA |
1mA |
|
|||
|
Measurement Mode |
Selectable:
Inductive (continuous test), Resistive (instantaneous test) or Auto (multiple
tests) |
||||||||||
|
Metal Type |
Selectable: Copper, Aluminum or Other Metal |
||||||||||
|
Alpha |
Programmable from 000.00 to 99.99 |
||||||||||
|
Temperature
Correction |
Manual or Automatic with 0.1° resolution |
||||||||||
|
Reference Temperature |
Programmable from 32° to 130°F or -10° to 130°C |
||||||||||
|
Ambient Temperature |
Programmable from 32° to 130°F or -10° to 130°C |
||||||||||
|
Temperature Probe |
100Ω platinum RTD |
||||||||||
|
Resolution |
0.1°F (0.1°C) |
||||||||||
|
Accuracy |
±0.9°F (±0.5°C) |
||||||||||
|
Alarms |
Two – programmable set points from 0.0 to 2500.0Ω |
||||||||||
|
Buzzer |
Programmable ON/OFF and volume level |
||||||||||
|
Power Source |
Rechargeable 6V, 8.5 Ah NiMH batteries; |
||||||||||
|
|
Approximately 5000 10A tests |
||||||||||
|
|
120/240VAC ± 20% (45 to 400Hz) line voltage |
||||||||||
|
Power Management |
Display powers down after 1, 5 or 10 minutes of inactivity
(operator selectable) |
||||||||||
|
Low |
is displayed when battery voltage is low |
||||||||||
|
Memory |
Stores up to 1500 test results |
||||||||||
|
|
Data in memory can
be reviewed on the instrument display, on a PC or via direct printout |
||||||||||
|
MECHANICAL |
|
||||||||||
|
Dimensions |
10.63 x 9.84 x 7.09" (270 x 250 x 180mm) |
||||||||||
|
Weight |
8.1 lbs (3.69kg) |
||||||||||
|
Index of Protection |
IP53 (case open); IP64 (case closed) |
||||||||||
|
DISPLAY |
|
||||||||||
|
Display Type |
Large 50,000-count digital |
||||||||||
|
Size |
4 x 2.25" (102 x 57mm) |
||||||||||
|
Backlight |
Blue electroluminescent |
||||||||||
|
Color |
Safety yellow case; gray faceplate |
||||||||||
|
COMMUNICATION |
|
||||||||||
|
|
PC, remote terminal, printer or trigger test from remote
contact closure |
||||||||||
|
ENVIRONMENTAL |
|
||||||||||
|
Operating
Temperature |
14° to 132°F (-10° to 55°C); 10 to 80% RH (non-condensing) |
||||||||||
|
Storage Temperature |
-40° to 140°F (-40° to 60°C) |
||||||||||
|
SAFETY |
|
||||||||||
|
Safety Rating |
EN 61010-1, 60V Cat. II |
||||||||||
|
Double Insulation |
|
|
Yes |
|
|||||||
|
CE Mark |
Yes |
||||||||||