The AEMC 5060 Digital/Analog 5000V Megohmmeter is the latest design in 5000V insulation testers. Features include automatic calculation and presentation of the Dielectric Absorption Ratio (DAR), Polarization Index (PI) and Dielectric Discharge (DD).
The AEMC 5060 displays the test voltage, insulation resistance and the leakage current during the test. Capacitance of the sample and discharge voltage present at the test leads is displayed at the conclusion of the test. This meter is designed with the highest level of built in safety features.
The AEMC 5060 can be operated from an internal rechargeable battery system or from an AC line power. The AEMC 5060 also, offers additional functionality in that an RS-232 port provides the ability to configure the unit from a PC and run the test from the PC. Test reports can be generated directly from the instruments to a printer or through the PC using the DataView® graphing and analysis software.
Applications:
What's Included:

The AEMC 5060 displays the test voltage, insulation resistance and the leakage current during the test. Capacitance of the sample and discharge voltage present at the test leads is displayed at the conclusion of the test. This meter is designed with the highest level of built in safety features.
The AEMC 5060 can be operated from an internal rechargeable battery system or from an AC line power. The AEMC 5060 also, offers additional functionality in that an RS-232 port provides the ability to configure the unit from a PC and run the test from the PC. Test reports can be generated directly from the instruments to a printer or through the PC using the DataView® graphing and analysis software.
Applications:
- Test insulation on cables, transformers, motors, generators, insulators and wiring installations
- High resistance or absorption tests
- Spot reading tests
- Timed resistance measurements
- Dielectric Absorption Ratio (DAR) and Polarization Index (PI) tests
- Multi-layer insulation testing (DD)
- Test old or water damaged installations over long time runs
- Motor insulation resistance measurements
- Computer controlled production line testing
- Predictive maintenance by storing results in PC for trend analysis
- User selectable voltage testing to provide application specific testing
What's Included:
- Three leads with integral 5kV rated hippo clips (red, blue and black)
- One jumper lead for use with guard terminal
- Rechargeable battery
- US 120V power cord
- Soft accessory bag
- User manual
- PC RS-232, DB9 F/F 6 ft null modem cable
- DataView® software.

The Good:
The Bad:
The Bottom Line:
The Bad:
The Bottom Line:
Full Review
- True Megohmmeter®
- Test voltage combination of 500V, 1000V, 2500V and 5000V
- Insulation measurements from 30kΩ to 10TΩ
- Adjustable and programmable test voltage (40 to 5100V)
- Automatic calculation of DAR, PI and DD values
- Direct measurement and display of Capacitance and Leakage Current
- Display resistance, test voltage and run time
- Programmable test run times and PI ratio times
- Smooth and Alarm functions
- Automatic test inhibition if live sample (>25)
- Automatic discharge and display of discharge voltage
- Large dual-display with time, voltage and measurements shown
- Bright blue electroluminescent backlight
- Programmable test voltage lock-out
- Programmable alarm setting
- Auto power-down when not in use
- AC or DC powered with rechargeable NiMH battery pack – run while charging
- Rugged weatherproof field case
- Designed and built to IEC safety standards
- EN 61010-1, 1000V Cat. III
- RS-232 interface for direct printing of results (serial or parallel output)
- 128kB memory for storing field test data
- Configure instrument and run tests from a PC
- Includes DataView® software for data storage, real-time display, analysis and report generation
Measurement Range
(1) Inhibit voltage is selectable at 3, 10 or 20% of test voltage
Display
Communication
General
| Test Voltage | 500V / 1000V/ 2500V/ 5000V |
| Measurement Range | 30kΩ to 2000GΩ (2TΩ) 100kΩ to 4000GΩ (4TΩ) 100kΩ to 10,000GΩ (10TΩ) 5000V 300kΩ to 10,000GΩ (10TΩ) |
| User Selectable Test Voltage | Programmable: 40 to 1000V: 10V increments; 1000 to 5100V: 100V increments |
| Accuracy | 1kΩ to 40GΩ ±5% of Reading ± 3cts 40GΩ to 10TΩ ±15% of Reading ± 10cts |
| Short Circuit Current | <3mADC |
| Voltage Test/Safety Check | 0 to 1000VAC/DC |
| Voltage Warning Indicator | Yes >25V |
| Test Inhibition(1) | Yes — adjustable from 25 to 1000V depending on test voltage range in use |
| Smooth Function (user selectable) | Digital filtering stabilizes display readings |
Display
| Backlight | Blue, Electroluminescent |
| Display Size | 4 x 2.25 " (102 x 57mm) |
| Digital Display | Two 4000-count displays |
| Analog Bargraph | 33-segments |
Communication
| Storage of Readings over Time R(t) | 128kB memory |
| Report Print Out Direct to Printer | Preset format |
| Storage of Test Results | Stores over 1500 test results |
| Communication Port | RS-232 |
| PC Software/Report Generation | Yes (included) |
General
| Power Source | 8 x NiMN rechargeable batteries |
| AC | 85 to 256VAC (50/60Hz) |
| Dimensions | 10.63 x 9.84 x 7.09" (270 x 250 x 180mm) |
| Weight | 7.7 lbs (3.5kg) |
| Protection Index | IP54 (NEMA 4X) |
The DataView® Software provides a convenient way to configure and
control Megohmmeter tests from your computer. Through the use of two
clear and easy-to-use dialog boxes, all functions of the AEMC 5060
Megohmmeter can be configured and tests can be initiated. Results can
be displayed in real time and stored in your PC. Reports can be
printed along with the operator’s comments and analysis.
Requirements:
Clear and easy setup of all functions from one tabbed dialog box.

Run test and display results from one dialog box.

A simple press of the download button from either the setup or run dialog boxes will show all test results stored in the AEMC 5060.

Each test will be stored as its own file and may be given its own unique file name.
- Print reports of all test results
- Select test voltage and run tests from your computer with a simple click and execute process
- Capture and display data in real time
- Retrieve data from the instrument’s memory
- Over 1500 insulation resistance measurements
- Over 4000 resistance measurements
- Display DAR and PI ratios
- Plot graphs of manual and timed tests
- Include your analysis in the comments section with the report
- Store a library of setups for different applications
Requirements:- Windows XP / Windows Vista / Windows 7 (32/64 bit)
- 256MB of RAM for Windows XP
- 1GB of RAM for Windows Vista & Windows 7 (32 bit)
- 2GB of RAM for Windows Vista & Windows 7 (64 bit)
- 80MB of hard disk space (200MB recommended )
- CD-ROM drive
Clear and easy setup of all functions from one tabbed dialog box.

Run test and display results from one dialog box.

A simple press of the download button from either the setup or run dialog boxes will show all test results stored in the AEMC 5060.

Each test will be stored as its own file and may be given its own unique file name.
Product brochures
Technical training
Product manuals